Three Phase - Inductive load (for transformers and non-resistive load)
Product ID: JK3PTS-XXXXX1. This controller protector: 1.The input main power loses the one phase. 2. The fuse break and checks the notice. 3. This controller heat sink exceeds temperature to protect. 4. Unusually output the contact, offer the distant place to monitor and use, the capacity 240VAC/5A of contact.
2. This controller is tally with CE international quality standard confirmation.
3. It has R.S.T. one phase’s fuse wire broken LED light, and offer a output point for abnormal condition, also can be emergency control for the system.
4. Cooling fans has temperature control, the cooling sheet working at 55C, and stop at 45C, this design can extend use-life of fans 2-3 times.
5. Applied load: IR lamp, quartz lamp, MoSi2, heater. Use of shoe-making machinery, plastic blow molding machines, plastic extrusion machinery, high vacuum thermo-evaporator machine, vacuum film-sputtering machine, vacuum sputtering PVD thin film deposition machine, heat treatment furnace, electric furnace, electric boiler, enameled wire machine, drawn work machinery, textile machinery, constant temperature and humidity systems.
Safety/Quality Approvals
3ø3W Phase angle
JK3PTS-22025, JK3PTS-22035, JK3PTS-22050,
JK3PTS-22060, JK3PTS-22080, JK3PTS-22100,
JK3PTS-22125, JK3PTS-22160, JK3PTS-22180,
JK3PTS-22200, JK3PTS-22225, JK3PTS-22250,
JK3PTS-22300, JK3PTS-22350, JK3PTS-22400, JK3PTS-22600, JK3PTS-22750
JK3PTS-48025, JK3PTS-48035, JK3PTS-48050,
JK3PTS-48060, JK3PTS-48080, JK3PTS-48100,
JK3PTS-48125, JK3PTS-48160, JK3PTS-48180,
JK3PTS-48200, JK3PTS-48225, JK3PTS-48250,
JK3PTS-48300, JK3PTS-48350, JK3PTS-48400, JK3PTS-48600, JK3PTS-48750
Three Phase Thyristor Power Regulator Of Inductive load English - Hand Book
- Main power: AC 220V 380~480V ±10%
- Auxiliary voltage: AC 220V±15% 50/60Hz
- Rated current: 25A 35A 50A 60A 80A 100A 125A 160A 180A 200A 225A 250A 300A 350A 400A 600A 750A
- Work frequency: 47~63Hz
- Output type: Phase Angle
- Phase angle input control signal: 4-20mA, 0-5V, 1-5V, 0-10V, 2-10V.
- Output range: 0~100%
- Environment: -10°C~50°C Humidity Under 90% RH.
- Insulation resistance: Over 20 MΩ (power & external cover) Over 20 MΩ (input signal & external cover).
- Strength of press-resisted: 2500VAC/1min between power & external cover 1000VAC/1min between power & external cover.
Replace the traditional magnetic switch, instant warm up, so that temperature to a minimum will not produce sparks and arc.